Parameter List
09.02
5-4
Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
5.2
General observation parameters
r001 Status
Observation parameters for the current status of the S/F unit
0 = Enter MLFB (P070)
(U)
1 = Establish factory setting
2 = Hardware initialization
(H)
4 = Hardware settings
(H)
5 = Drive system settings
(A)
7 = Fault
(B)
8 = Restart inhibit
(B)
9 = Ready for turn-ON
(B)
10 = Wait for system voltage
(B)
11 = Ready for operation
(B)
12 = Ground fault test
(B)
14 = R/R unit is in operation
(R)
15 = Ramp generator decelerating (OFF1)
(R)
18 = Circuit identification or forming
(R)
21 = Download of parameter settings
(B)
PNU=1Hex; Type=O2;
Scaling:
1Hex
=
∧
1
0 to 21
MLFB-Input
Init. RFE
InitHW Conf
HW Config.
System Set.
Fault
ON Locked
Ready for ON
Line Voltage
Ready Oper
GrndFltTest
Operation
OFF 1
Circuit ID
Download
- 2/UHABR
r006
DC Bus Volts
Actual DC link voltage
PNU=6Hex; Type=I2;
Scaling:
1Hex
=
∧
1 V
0 - 100%
=
∧
0 to 16384V
0 to 1000
[V]
-
-
2/ BR
r011 Heatsink
Temp
Temperature of the heat sink
PNU=0BHex; Type=I2; Scalling:
1Hex
=
∧
1
°
C PZD gr.: 1
Analog output: +/-100%
=
∧
+/-100
°
C
-53 to 199
[
°
C]
-
-
3/ BR
r012 Base/Reserve
Base / reserve settings of the process data wiring for control word bits
0: Base
setting
1: Reserve
setting
PNU=0CHex; Type=O2;
Scaling:
1Hex
=
∧
1
0 to 1
-
-
2/ BR
r013 Operat.
Hours
Display of operating hours with firing pulses enabled (Run status).
All times > about 0.1s are taken into account.
i001 = days (0..9999)
i002 = hours (0..24)
i003 = seconds (0..3600)
The operating hours counter r013 is set to 0 when the factory setting is
established (P052=1).
PNU=0DHex; Type=O2;
Scaling:
1Hex
=
∧
1
d
h
s
3
-
2/ BR
r030 Rectifier
Volts
Display of the system voltage at the rectifier bridge (phase W-U)
PNU=1EHex; Type=O2;
Scaling:
1Hex
=
∧
0.1 V
0 - 100%
=
∧
0 to 1638.4V
0.0 to 1000.0
[V]
-
-
2/ BR
r031 Inverter
Volts
Display of the system voltage at the regenerative bridge (average value of
the three phases)
PNU=1FHex; Type=O2;
Scaling:
1Hex
=
∧
0.1 V
0 - 100%
=
∧
0 to 1638.4V
0.0 to 1000.0
[V]
-
-
2/ BR