09.02
Parameter List
Siemens AG 6SE7087-6AK85-1AA0
5-5
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
r032 Line
Frequency
Display of the line frequency
PNU=20Hex; Type=O2;
Scaling:
1Hex
=
∧
0.01 Hz,
0 - 100%
=
∧
0 to 50 Hz PZD gr.: 1
0.01 to 65.00
[Hz]
-
-
2/ BR
r033 Firing
Angle
Display of the firing angle
PNU=21Hex; Type=O2;
Scaling:
1Hex
=
∧
0.1
°
el,
0 - 100%
=
∧
0
°
el -180
°
el PZD gr.: 1
0.0 to 165.0
[
°
el]
-
-
2/ BR
r034
DC Amps (set)
Display of DC link current setpoint
PNU=22Hex; Type=I2;
Scaling:
1Hex
=
∧
0.1 %,
±
100%
=
∧
±
P075
PZD gr.: 1
-150 to 150
[%]
-
-
3/ BR
r035
DC Amps (act)
Display of actual DC link current
PNU=23Hex; Type=I2;
Scaling:
1Hex
=
∧
1 %,
±
100%
=
∧
±
P075
PZD gr.: 1
-199 to 199
[%]
-
-
2/ BR
r036
DC Volts (set)
Display of DC link voltage setpoint
The setpoint 1.35
*
r030, limited to values of P074 up to 106.8%.
PNU=24Hex; Type=O2;
Scaling:
1Hex
=
∧
1 %, 100%
=
∧
1.35
*
P071
PZD gr.: 1
0 to 199
[%]
-
-
3/ BR
r037
DC Volts (act)
Display of actual DC link voltage
PNU=25Hex; Type=O2; Scaling: 1Hex
=
∧
1 %, 100%
=
∧
1.35
*
P071
PZD gr.: 1
0 to 199
[%]
-
-
2/ BR
r038
DC Volts Deviat.
Display of setpoint/actual-value deviation of DC link voltage controller
PNU=26Hex; Type=I2;
Scaling:
1Hex
=
∧
1 %, 100%
=
∧
1.35
*
P071
PZD gr.: 1
-199.9 to 199.9
[%]
-
-
3/ BR
r039 AnalogOut
Displ.
Display of terminal X102-14 (analog output)
PNU=27Hex; Type=O2;
Scaling:
1Hex
=
∧
0.1,
±
100%
=
∧
±
10V at terminal
X102-14
PZD gr.: 1
-112.1 to 112.1
[%]
-
-
2/ BR