09.02
Parameter List
Siemens AG 6SE7087-6AK85-1AA0
5-3
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
5.1 Operation
display
r000 Operation
Display
Status display, faults and warnings of the S/F unit
For description, see Chapter 6 Operator control
o014 Run
- -
No thyristor bridge in circuit
I
Rectifier bridge in circuit
II
Regenerative bridge in circuit
o012 Test
phase
Wait until the thyristor test and/or earth-fault test has been
completed (Selection function: P353
≠
0 and/or P354
≠
0).
Note: The thyristor test can only be conducted if the DC link
voltage is less than 5% of 1.35
*
P071. Following an ON
command, therefore, wait in operating status o012 until this
condition is satisfied!
o011 Wait for Run enable
Wait for Run enable
o010
Wait for system voltage
Wait until the system voltage has been checked.
or
Wait for voltage at power terminals X1-U1, X1-V1, X1-W1
(rectifier bridge)
or
Wait for voltage at power terminals X4-1U2, X4-1V2, X4-1W2
(regenerative bridge)
or
Wait for checkback signal "System contactor energized"
or
Waiting state before energizing the system contactor (Waiting
time P409)
o009
Wait for Ready to Switch On
Wait for Ready to Switch On (OFF1 active)
or
Wait until internal OFF state is canceled by an external OFF
command.
o008
Switch-on inhibit; isolation (OFF2)
Wait for acknowledgment of switch-on inhibit by activating the
SWITCH-OFF command
or
Isolation implemented (OFF2)
or
Wait until a valid USS telegram to SST1 has been received
(only if P687 is set to
≠
0)
or
Wait until a valid peer-to-peer telegram to SST2 has been
received (only for P688=1, when P687.i003 is set to
≠
0)
o007
Fault
A fault message has been received.
o021
Download
A parameter download over SST1 can be executed
o005 Drive
settings
o004 Hardware
settings
o002
Electronics initialization
The option module electronics are initialized
or
The basic unit electronics are initialized
o001 Establish factory setting
o000 Set
MLFB
PNU=00Hex; Type=O2;
Scaling:
1Hex
=
∧
1
0 to 21
-
-
1/UHABR