Parameter List
09.02
5-6
Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
5.3 General
parameters
P050
*
Language
Display language on the optional operation panel OP
0: German
3: Français
1: English
4: Italiano
2:
Espanol
PNU=32Hex; Type=O2;
Scaling:
1Hex
=
∧
1
0 to 4
German
English
Espanol
Français
Italiano
-
0
2/UHABR
2/ HABR
P051
*
Access Level
Setting of access levels; with higher access levels more parameters can be
read and/or written.
1:
Operating via PMU or OP
2: Standard
mode
3: Expert
mode
PNU=33Hex; Type=O2;
Scaling:
1Hex
=
∧
1
1 to 3
Operation
Standard
Expert
-
2
1/UHABR
1/UHABR
P052
*
Function Select
Selection of several commissioning steps and special functions.
(See Section 4.3.9 for details)
0 = Return from on of the functions described below to the previous
status of the R/R unit
1 = Parameter-Reset: all parameters are reset to their original
settings (factory settings).
According to the Profibus profile for variable speed drives this
function is also accessible via parameter P970. After finishing
this function the parameter is automatically reset to 0.
2 = Release for MLFB setting (changing into the status 'MLFB
input'). To exit this function the parameter must be reset to 0.
3 = Upread/Download (Changing into the status
'Upread/Download'). To exit this function the parameter must be
reset to 0.
4 = Hardware configuration (Changing into the status 'Hardware
settings'). To exit this function the parameter must be reset to 0.
5 = Drive setting (change to the status "Drive setting" for assigning
the plant data parameters. To exit this function the parameter
must be reset to 0.
20 = Forming of the DC link
21 = Circuit identification: Assigning the controller parameters of the
R/R unit
22 = Display only parameters with modified values
Important
: This function can only be used in conjunction with
operator control from the PMU. To exit this function the
parameter must be reset to 0 (Return).
PNU=34Hex; Type=O2;
Scaling:
1Hex
=
∧
1
0 to 22
Return
Param.Reset
Input MLFB
Upread/Download
HW Config.
System Set.
FormingCaps
Circuit ID
Changed Par
-
0
2/UHABR
2/UHAB