09.02
Start-Up
Siemens AG 6SE7087-6AK85-1AA0
4-25
Rectifier/Regenerating Unit Operating Instructions
4.3.1.2.3
Selecting the destinations for the status word
(bits 0 - 31)
For the selection parameters
P600 to P631
, in which the destination of the appropriate bit can be specified,
then the indices are uniformly assigned as follows:
Index i001
Selecting a terminal on the CUR board (basic converter)
i002
Selecting a terminal on the SCI 1/2 board (option)
Index i001
Selecting a terminal on the CUR board (basic converter)
Value Destination
0000 No
destination
Factory setting, except P603
1001
CUR, BA1, -X104:17/18,
1002
CUR, BA2, -X104:19/20,
Factory setting, for P603
Index i002
Selecting a terminal on the SCI 1/2 board (option)
Value Destination
0000 No
destination
Factory setting
4101
SCI 1 and 2,Slave 1, BA1
4102 BA2
4103 BA3
4104 BA4
4105 BA5
4106 BA6
4107 BA7
4108 BA8
4109
only SCI 2,Slave 1, BA9
4110 BA10
4111 BA11
4112 BA12
4201
SCI 1 and 2,Slave 2, BA1
4202 BA2
4203 BA3
4204 BA4
4205 BA5
4206 BA6
4207 BA7
4208 BA8
4209
only SCI 2,Slave 2, BA9
4210 BA10
4211 BA11
4212 BA12