09.02
Parameter List
Siemens AG 6SE7087-6AK85-1AA0
5-7
Rectifier/Regenerating Unit Operating Instructions
PNU
*
: Conf.
Par.
OP1S parameter name
Description
Value range
[phys. unit]
Selection text
Display
Indices
Factory-
setting
See
Modify
(access /
status)
P053
*
Parameter Access
Release of interfaces for parameterization.
This parameter is also available as P927 in keeping with Profibus Profile
DVA.
0: none
1: COM BOARD
(CB)
2: BASE KEYPAD
(PMU)
4: BASE SERIAL (SST1)
(SST1 and OP)
8: Serial I/O (SCB with USS))
(SCB)
16: TECH
BOARD
(TB)
Description for Setting:
Every interface is coded by a number.
Input of the number or the total of several numbers which are related to
interfaces, gives parameterization access to these interfaces.
Example:
The factory setting '6' (=4+2) means, that BASE KEYPAD (PMU) and
BASE SERIAL (SST1) have parameterization access.
PNU=35Hex; Type=O2;
Scaling:
1Hex
=
∧
1
0 to 31
-
6
1/UHABR
1/
HABR
P054 Display
Light
Backlight for the optional operation panel OP
0 = Backlight always ON
1 = Backlight only ON during operation
PNU=36Hex; Type=O2;
Scaling:
1Hex
=
∧
1
0 to 1
always ON
dur. operat.
-
0
3/ BR
3/ BR
P055
*
Copy Parameters
This parameter permits the
copying
of data sets 1, 2, 3 or 4 to data sets 1,
2, 3 or 4.
Only those parameters specified in Section 4.4 "Selecting the data sets" are
affected by the copying process whereby each of these parameters has 4
indices that are assigned to the 4 data sets.
Data set 1 can be set with the parameters Pxxx i001
Data set 2 can be set with the parameters Pxxx i002
Data set 3 can be set with the parameters Pxxx i003
Data set 4 can be set with the parameters Pxxx i004
0xy
Do nothing;
automatic reset value at the end of a copy
operation
1xy The contents of data set x (x = 1, 2, 3 or 4) are
copied
to data
set y (y = 1, 2, 3 or 4) (data set x remains unchanged; the
original contents of data set y are overwritten).
x and y are the respective data set numbers (1, 2, 3 or 4) of the
source and destination data set.
Each copy operation is started by changing P055 to parameter mode if
P055 = xy and the unit is not in the "RUN" status. P555 is reset to P055 =
0xy at the end of the copy operation.
Important
: Once a copy operation has been started, the electronic
power supply must not be switched off for at least 3 minutes to
enable the copied parameters to be passed to the EEPROM.
P055 is not stored in the EEPROM, and has the value "012" when the
electronic power supply is switched on.
PNU=37Hex; Type=L2;
Scaling:
1Hex
=
∧
1
011 to 144
-
012
3/ B
3/ B