Operating the circuit-breaker panel
139-2021.9 / 07
NXAIR M
45
10.12 Opening the circuit-breaker manually
NOTICE
Conflicting operation
The requirement of setting the panel to either local or remote control prevents
operating the panel locally and centrally at the same time.
For operating the circuit-breaker manually, set the panel to local control,
for example by switching the local-remote switch to LOCAL position.
HINT
Unexpected motor noise and vibration
Operating the circuit-breaker discharges and/or charges the spring energy store
abruptly. This causes a short loud noise and low vibration.
Expect switching noise and low vibration from inside the circuit-breaker.
HINT
The opening spring is charged during the closing operation.
Preconditions
Withdrawable circuit-breaker in service position or in test position
Circuit-breaker in CLOSED position
High-voltage door closed
Panel set to local control
Padlock (optional) removed from actuating opening
Push rod available
Fig. 62: High-voltage door with actuating opening