Operating the circuit-breaker panel
38
NXAIR M
139-2021.9 / 07
Preconditions
Withdrawable circuit-breaker in service position
Circuit-breaker in OPEN position
Racking crank for moving the withdrawable circuit-breaker available
Double-bit key available
Padlock (optional) removed from operating slide
For electromagnetic interlock (optional):
Electromagnetic interlock deactivated
For panels with removable voltage transformers (optional):
Removable voltage transformers racked to test position
The actuating opening for racking the withdrawable circuit-breaker is located on the control board of the
high-voltage door.
Fig. 48: Actuating opening for
racking the withdrawable
circuit-breaker
Fig. 49: Racking crank
Fig. 50: Double-bit key,
diameter 5 mm
Procedure
NOTICE
Maloperation
All interlocks are only released when the withdrawable part is in a stable end
position.
Rack the withdrawable circuit-breaker absolutely until end position.
Lift the operating slide and hold it.
To release access to the withdrawable circuit-breaker, insert the double-bit key and turn
counter-clockwise as far as it will go (that is
90°).
Fig. 51: Releasing access to the withdrawable part