Operating the double-busbar system
102
NXAIR M
139-2021.9 / 07
14.5 Opening or closing the high-voltage door
The procedure for opening and/or closing the high-voltage door at the circuit-breaker panel for double-busbar
system is identical with the procedure for opening and/or closing the high-voltage door at the circuit-breaker
panel version for single-busbar system.
For opening and/or closing the high-voltage door at the circuit-breaker panel for double-
busbar system, see chapter 10.4 and/or 10.5.
14.6 Positions of the withdrawable circuit-breaker
The positions of the circuit-breaker in the circuit-breaker panel for double-busbar system are identical with
the positions of the circuit-breaker in the circuit-breaker panel version for single-busbar system.
For the circuit-breaker positions in the circuit-breaker panel for double-busbar system, see
chapter 10.6.
14.7 Racking the withdrawable circuit-breaker
HINT
In the panel version for double-busbar system, the withdrawable parts in the
panels A and B are generally interlocked electromagnetically against the position
of the feeder earthing switch in panel A.
Observe the release of the actuating opening for racking the withdrawable
parts.
The procedure for racking the withdrawable circuit-breaker to service position and/or test position in the
circuit-breaker panel for double-busbar system is identical with the procedure for racking the withdrawable
circuit-breaker to service position and/or test position in the circuit-breaker panel version for single-busbar
system.
For racking the withdrawable circuit-breaker to service position and/or test position in the
circuit-breaker panel for double-busbar system, see chapter 10.7 and/or 10.8.
14.8 Closing or opening the circuit-breaker
The procedure for closing and/or opening the circuit-breaker in the circuit-breaker panel for double-busbar
system is identical with the procedure for closing and/or opening the circuit-breaker in the circuit-breaker
panel version for single-busbar system.
For electrical closing and/or opening of the circuit-breaker in the circuit-breaker panel for
double-busbar system, see chapter 10.9
and/or
10.10.
For manual closing and/or opening of the circuit-breaker in the circuit-breaker panel for
double-busbar system, see chapter 10.11
and/or
10.12.
14.9 Discharging or charging the closing spring
The procedure for discharging and/or charging the closing spring in the circuit-breaker panel for double-
busbar system is identical with the procedure for discharging and/or charging the closing spring in the circuit-
breaker panel version for single-busbar system.
For discharging and/or charging the closing spring in the circuit-breaker panel for double-
busbar system, see chapter 10.13
and/or
10.14.