Operating the circuit-breaker panel
139-2021.9 / 07
NXAIR M
57
If no withdrawable circuit-breaker is inserted in the panel and no further operation is
executed: Close the high-voltage door.
The removed low-voltage connector is lying in the support located underneath the low-
voltage compartment.
10.18 Plugging on the low-voltage connector
HINT
Unexpected motor noise and vibration
When auxiliary voltage is applied, a motor inside the circuit-breaker starts
immediately after plugging on the low-voltage connector in order to charge the
spring energy store. This is a permissible operating state.
Expect motor noise and low vibration.
Preconditions
Withdrawable circuit-breaker in test position
Spring energy store in the circuit-breaker discharged
Auxiliary voltage for the panel disconnected
High-voltage door open
Low-voltage connector stowed away
Procedure
HINT
In addition to these instructions, an instruction label on the withdrawable circuit-
breaker informs about plugging on the low-voltage connector.
Follow the advice on the label (3) to push the longitudinal fastener.
Fig. 89: Instruction label on withdrawable circuit-breaker