Verifying safe isolation from supply
132
NXAIR M
139-2021.9 / 07
16.7 Verifying safe isolation from supply with the CAPDIS or VOIS device system
DANGER
Electric shock
Always verify safe isolation from supply without any doubt
If safe isolation from supply is verified erroneously although operational high
voltage is still applied, there is danger to life.
Before performing any kind of checks or work in the busbar compartment
or the connection compartment of each panel, verify safe isolation from
supply in these compartments without any doubt.
Observe the
Five Safety Rules
.
Preconditions
High-voltage door closed
Door to low-voltage compartment closed
Indication "Operational high voltage not present" visible
Safe isolation from supply is verified as soon as L1, L2 and L3 have been
determined to be isolated from supply.
16.8 Supplier information
Further information for the devices to get from:
Device
Supplier:
VOIS+ / VOIS-R+ /
CAPDIS-S1+ / CAPDIS-S2+
www.kries.com
LRM system
www.horstmanngmbh.com
LRM-ST voltage indicator
Siemens AG / Order No.: 8DX1620