Panels with motor operating mechanism control
139-2021.9 / 07
NXAIR M
227
The procedure for opening the circuit-breaker manually in panels with motor operating mechanism control is
identical with the procedure in panels without motor operating mechanism control.
For opening the circuit-breaker manually, see chapter 10.12.
23.12 Closing the circuit-breaker manually
Closing the circuit-breaker manually is carried out by pushing a rod through an actuating opening in the high-
voltage door, thereby operating the ON pushbutton underneath the high-voltage door. In contrast to manually
opening the circuit-breaker, closing is only possible when the control door is open. However, the indicator for
the circuit-breaker position can still be seen through an inspection window after closing the control door.
Fig. 381: Circuit-breaker type 3AE1:
actuating opening for closing the
circuit-breaker manually
Fig. 382: Circuit-breaker type 3AE5:
actuating opening for closing the
circuit-breaker manually
Fig. 383: Circuit-breaker type 3AE1:
inspection window for
CLOSED/OPEN indicator of the
circuit-breaker
Fig. 384: Circuit-breaker type 3AE5:
inspection window for
CLOSED/OPEN indicator of the
circuit-breaker