Operating the circuit-breaker panel with HV HRC fuse
139-2021.9 / 07
NXAIR M
87
13.10 Plugging on the low-voltage connector
HINT
Unexpected motor noise and vibration
When auxiliary voltage is applied, a motor inside the circuit-breaker starts
immediately after plugging on the low-voltage connector in order to charge the
spring energy store. This is a permissible operating state.
Expect motor noise and low vibration.
Preconditions
Withdrawable circuit-breaker / fuse combination in test position
Spring energy store in the circuit-breaker discharged
Auxiliary voltage for the panel disconnected
High-voltage door open
Low-voltage connector hanged down on the side wall
Procedure
HINT
In addition to these instructions, an instruction label on the withdrawable circuit-
breaker / fuse combination informs about plugging on the low-voltage connector.
Follow the advice on the label (3) to push the longitudinal fastener.
Fig. 140: Instruction label on withdrawable circuit-breaker / fuse combination
Take the low-voltage connector out of the support located on the left side.