Accessing the connection compartment through the front
174
NXAIR M
139-2021.9 / 07
Fig. 300: 6 bolted joints on bushing plate with bushings
Fasten the 3 connecting cables (8) for the removable voltage transformers at the cable
connections.
Fig. 301: Bolted joints at the cable connections
Insert the partition (2), and fasten with 8 bolts M8x20 with contact washers and plain
washers.
Tighten the bolts with torque 25 Nm.
Fig. 302: 8 bolted joints on partition