Accessing the connection compartment through the front
139-2021.9 / 07
NXAIR M
157
HINT
Final procedure steps
Now the panel can be integrated into the course of operation again, for example:
Inserting the withdrawable part in the panel.
Closing the high-voltage door.
De-earthing the feeder.
Racking the withdrawable part to service position.
19.4 Accessing the connection compartment through the switching-device compartment in panel
versions with ventilation system
WARNING
Reduced safety
The closed connection compartment is an important safety element of the
switchgear. The connection compartment is exclusively opened for performing
operational activities inside the connection compartment.
Always install the partition between the connection compartment and the
switching-device compartment:
If an activity inside the connection compartment is interrupted.
Immediately after an activity inside the connection compartment was
completed.
CAUTION
Sharp edges
The metal parts of the ventilation duct and the vertical partition may have sharp
edges.
Put on personal protective equipment.
CAUTION
High weight
The ventilation duct is heavy.
Remove the ventilation duct absolutely with 2 persons.
Put on personal protective equipment.