Operating the circuit-breaker panel with HV HRC fuse
92
NXAIR M
139-2021.9 / 07
Replacing HV HRC fuse-links
NOTICE
Undetected damage
Tripped HV HRC fuse-links can cause hidden damages on the other
HV HRC fuse-links.
Always replace all HV HRC fuse-links, even if only one HV HRC fuse-link
has tripped.
HINT
Electrical indication of tripped fuse-links
Electrical indications at the panel or in the remote control room are
not
automatically reset to operating mode by replacing the HV HRC fuse-links.
HINT
Recommended order of action
The HV HRC fuse-link in the middle phase L2 are only accessible after removing
the HV HRC fuse-links from the neighboring phase L1 or L3.
First, remove the HV HRC fuse-links from the outer phases L1 and L3 on
the left and right side of the circuit breaker / fuse combination. Then go on
to remove the HV HRC fuse-links from the middle phase L2.
Preconditions
Set of proper HV HRC fuse-links available
Withdrawable circuit breaker / fuse combination taken out of the panel
High-voltage door closed
Procedure
When the withdrawable part is taken out of the panel, fuse assemblies are accessible for the replacement of
the HV HRC fuse-links.
HINT
Hereafter, the disassembly of those parts is described, which are later assembled
again at the same place.
Store disassembled parts carefully and keeps them available for later
reuse.