Operating the circuit-breaker panel
139-2021.9 / 07
NXAIR M
51
10.15 Earthing the feeder manually
NOTICE
Maloperation
A switching operation once started must be completed totally! A switching
operation that was not completed cannot be turned back.
Do not try to remove the operating lever at intermediate positions.
NOTICE
Maloperation
If the operating lever is not inserted correctly, the feeder earthing switch may be
damaged.
Insert the operating lever in the actuating opening as far as it will go.
Instruction label on high-voltage door:
In addition to these instructions, an instruction label on the high-voltage door informs about proper handling
of the operating lever for the feeder earthing switch.
Fig. 72: Instruction label on high-voltage door
Preconditions
High-voltage door closed
Feeder to be earthed is isolated
Withdrawable circuit-breaker in test position
Operating lever available
Padlock (optional) removed from operating slide
For electromagnetic interlock (optional):
Electromagnetic interlock deactivated