Accessing the connection compartment through the front
139-2021.9 / 07
NXAIR M
153
All panel versions:
Remove the connecting elements from the partition (3) to the connection compartment inside
the switching-device compartment, and store them:
15 bolts M8x20 with contact washers and plain washers
Remove the partition (3), and store it.
Fig. 261: 15 bolted joints on partition in circuit-breaker panel,
panel spacing 800 mm
Access to the connection compartment through the panel front is given.
HINT
Final procedure steps
Immediately proceed to perform the intended checks and works in the
connection compartment.
19.3 Installing the vertical partition in the switching-device compartment
DANGER
Electric shock
To perform any kind of activities inside or near the connection compartment of a
panel, you must ensure that this compartment is safely isolated from supply.
Without isolation from supply, the cables / bars in the connection compartment will
be live at operational high voltage.
Observe the
Five Safety Rules
.
Verify safe isolation from supply.
Do not
operate the feeder earthing switch during any activities inside or
near the connection compartment.