The information required to configure the TriSpector1000 in the programmable con‐
troller consists of the following:
Name
TriSpector
Comm Format
Data - SINT (Single-INTeger)
IP Address
192.168.1.30
Assembly Instance
Size
Input
101
494
Output
100
130
Configuration
1
0
Input
is data from the TriSpector1000 to the programmable controller.
Output
is data from the programmable controller to the TriSpector1000.
The data exchanged between the TriSpector1000 and the programmable controller
includes one Input Assembly Instance and one Output Assembly Instance with the sizes
shown. The Configuration Assembly is just a dummy and is not actually used. The con‐
nection will also use Unicast messaging.
After the ‘Generic Ethernet Module’ has been configured for the TriSpector1000, three
tag databases will be generated within the programmable controller’s ‘Controller Tags’.
Again, the ‘Configuration’ is a dummy and is not used. Emphasis should be placed on
the Input and Output Tag Databases generated by this ‘Generic Ethernet Module’ con‐
figuration.
12.5.2.1
Input Data Format
The Input Data Format is described in the following table. This table shows the Byte
allocation as well as the Bit description for the entire Input Data Format for the TriSpec‐
tor1000.