X100
X10
X1
Description
2
5
5
DHCP mode activated.
8
8
8
IP address reset
A standard IP address is used. If the IP address was changed with
other methods (e.g. web interface), the IP address will be reset to
default IP address 192.168.0.1 when the master reboots.
9
1
1
Safe mode
This mode is used to deactivate the Dual Talk services.
The safe mode deactivates:
- Web interface
- OPC UA
- MQTT
- REST API
The previously saved settings for fieldbus protocols are not
affected by this position, so communication will start even if you
leave the switches in this position. However, setting the positions
to the previous state is recommended.
9
1
3
Deactivation of WebUI and REST API
9
7
9
Factory reset
The device performs a factory reset. This also resets the network
parameters to the default values. No communication is possible in
this operating mode.
The IP address is deleted and the device is in
BootP
mode.
7.4
Data security
Proper project and other planning is an important prerequisite for ensuring the confi‐
dentiality, availability and integrity of data.
EtherCAT products are intended for use in local networks. Observe the following notes
when using EtherCAT products in your plant:
•
Do not connect control components and control networks to an open network
such as the Internet or an office network.
•
Protect the control components and control networks with the use of a firewall.
•
Close all services not required by your application (
) to
reduce the risk of cyber attacks and thus increase cyber security.
•
Restrict physical and electronic access to all automation components to an
authorized group of persons.
•
To reduce the risk of unauthorized persons gaining access to your system, be sure
to change the default passwords and IP addresses before initial commissioning.
7
COMMISSIONING
26