7.2
MAC address
Each device has a uniquely assigned MAC address that cannot be changed by the user.
The assigned MAC address is printed on the module.
7.3
Rotary switch
The SIG350 has three rotary switches on the lower side of the SIG350 with which
various settings can be made manually. These include setting the last octet of the IP
address, but also performing a factory reset.
In the delivery state, the rotary switches are set to: 000.
!
"
#
$
%
&
'
(
!
"
#
$
%
&
'
(
!
"
#
$
%
&
'
(
x100
x10
x1
Figure 11: Rotary switch position in delivery state
To change settings in the module using the rotary switches, proceed as follows:
1
Set the rotary switch to the desired position.
2
Disconnect the module from the voltage supply.
3
Supply the module with voltage again.
4
Wait at least 10 seconds until the settings are loaded.
The new settings are then accepted and saved in the module.
Exception:
The procedure is different for rotary switch setting
979
(factory settings):
1
Disconnect the module from the voltage supply.
2
Set the rotary switch to position 979.
3
Supply module with voltage.
4
Wait at least 2 minutes until the settings are loaded.
5
Disconnect the module from the voltage supply again.
6
Set the rotary switch to position 000 or another desired position.
7
Reconnect the module to the voltage supply.
NOTE
The previously saved settings for fieldbus protocols are not affected by this position.
Communication is then started if the switches are left in this position.
However, setting the positions to the previous state is recommended.
Table 9: Meaning of rotary switch settings
X100
X10
X1
Description
0
0
0
Delivery state
The default network configuration is used:
- BootP active
When the IP address is changed, the last saved address is used.
0
0
1
Manual IP address
With switch settings 0-0-1 ... 2-5-4, a fixed IP address can be set
manually:
The last octet of the preset IP address is set here (default:
192.168.0.xxx).
…
…
…
2
5
4
COMMISSIONING
7
8027836./2022-06-10 | SICK
O P E R A T I N G I N S T R U C T I O N S | Sensor Integration Gateway - SIG350
25