Mounting
Figure 4: Mounting the ground strap
•
Place the ground strap in the opening provided in the housing for functional earth.
•
Position washer on ground strap and fasten to module with M4 screw.
•
Observe the tightening torque of 1.2 Nm.
•
Align ground strap
•
Tighten the lower end of the ground strap with another M4 screw and two washers
at the mounting location, observing the tightening torque.
5.4
Rotary switch cover
The rotary switches are provided with a cover to ensure IP protection. To operate the
rotary switches, the cover must be removed. The cover must then be refitted.
The rotary switch cover is fastened with two M3 screws. The permitted tightening torque
is 0.8 Nm.
5
MOUNTING
18
O P E R A T I N G I N S T R U C T I O N S | Sensor Integration Gateway - SIG350
8027836./2022-06-10 | SICK