34
Selected
value
Event input function
Input ON
(Closed)
Input OFF
(Open)
Remarks
008
Auto/Manual control
Manual
control
Automatic
control
009
Remote/Local
Remote
Local
Effective only when
EA or EV
option is added
010
Program mode;
RUN/STOP
RUN
STOP
Level action when
power is turned on
011
Program mode;
Holding/Not holding
Holding
Not holding
Level action when
power is turned on
012
Program mode;
Advance function
Advance
Standard
control
Level action when
power is turned on
013
Integral action holding
Integral action
Holding
Standard
integral
action
Control continues
with the integral
value being held.
014
Preset output 2
Preset output
(*2)
Standard
control
The unit maintains
control with the
preset output MV.
Signal edge action from OFF to ON or from ON to OFF is engaged.
If “010 (Program mode RUN/STOP)” is selected in [Event input EVI1 allocation], the
following action will be performed. However, only when power is turned ON, Level
action [ON (Closed) or OFF (Open)] is engaged.
OR calculation [if any one is ON (closed), the function activates] begins if the same
functions except “001(Set value memory)” have been selected for plural Event inputs.
(*1) The value that 1 (one) is added to 2
n
, is indicated on the MEMO/STEP Display.
(e.g.) If EVI1(2
0
)=OFF, EVI2(2
1
)=ON, then 3 (2
1
+1) is indicated.
2
0
, 2
1
, 2
2
and 2
3
will be allocated to Event input EVI1 to EVI4 respectively, and
the Set value memory number will be determined by each value of EVI1 to EVI4.
(Refer to Section “9.7 Set Value Memory Function” on p.72.)
(*2) Preset value can be set in [Preset output] (p.30) in the Output group.
11-15 [DI1(EVI1)-COM]:
OFF(Open)
Standby mode
Standby mode
11-15 [DI1(EVI1)-COM]:
ON(Closed)
Program control performs.
Program control Run
Program control Stop
(in Standby mode)
11-15 [DI1(EVI1)-COM]:
OFF(Open)
Program control stops
(in Standby mode).
11-15 [DI1(EVI1)-COM]
OFF (Open)
Program control performs when
“11-15 [DI1(EVI1)-COM]” changes
from OFF(Open) to ON(Closed).
Program control stops (in standby mode)
when “11-15 [DI1(EVI1)-COM]” changes
from ON(Closed) to OFF(Open).
11-15 [DI1(EVI1)-COM]
ON (Closed)
Controller status
(Fig. 7.3.3-1)