30
7.3.2 Output Group
To enter the Output group, follow the procedure below.
(1)
Press the
key 4 times in PV/SV Display Mode.
The unit will enter the Engineering group.
(2)
Press the
key. The unit will proceed to the Input group.
(3)
Press the
key. The unit will proceed to the Output group.
(4)
Press the
key.
The unit will proceed to the ‘MV high limit’.
Character
Name, Function, Setting Range
Factory Default
MV high limit
100%
• Sets the MV high limit value.
Not available for ON/OFF control
• Setting range: MV low limit value to 100%
MV low limit
0%
• Sets the MV low limit value.
Not available for ON/OFF control
• Setting range: 0% to MV high limit value
ON/OFF hysteresis
1.0
• Sets ON/OFF hysteresis.
Available only for ON/OFF control
• Setting range: 0.1 to 1000.0 ( ),
DC voltage, current inputs: 1 to 10000 (The placement of the decimal
point follows the selection.)
Direct/Reverse action
Reverse (Heating) action
• Selects either Reverse (Heating) or Direct (Cooling) control action.
•
: Reverse (Heating)
action
: Direct (Cooling) action
Preset output
0.0%
• If the Preset output 1 or 2 is selected in [Event input allocation], MV can
be set.
Preset output 1
:
Control is performed with the preset MV if sensor is burnt out during
Event Input ON.
Preset output 2
:
Control is performed with the preset MV when Event Input is ON.
• Available only when EI option is added.
• Setting range:0.0 to 100.0%
FBP Yes/No
FBP Yes
• Selects FBP (feedback potentiometer) Yes or No.
•
: FBP Yes
: FBP No
Open/Closed output dead band
10%
• Sets Open/Closed output dead band.
Not available if “FBP No” is selected in [FBP Yes/No].
• Setting range: 0 to 100%