86
External setting input (option code:
EA , EV )
SV adds external analog signal to remote bias value.
Setting signal: Direct current: 4 to 20 mA DC [Option code: EA1]
0 to 20 mA DC [Option code: EA2]
DC voltage: 0 to 1 V DC [Option code: EV1]
1 to 5 V DC [Option code: EV2]
Allowable input: EA : 50 mA DC max.
EV1: 5 V DC max.
EV2: 10 V DC max.
Input impedance: EA : 50
EV : 100 k
Input sampling period: 250 ms
Transmission output (option code:
TA1, TV1)
Converting the value (PV, SV, MV or DV transmission) to analog signal every 125ms,
outputs the value in current or voltage. (Factory default: PV transmission)
Outputs Transmission output low limit value (4 mA DC or 0 V DC) if Transmission output
high limit and low limit value are the same.
Resolution:
12000
Output:
4 to 20 mA DC (load resistance, Maximum 500 )
0 to 1 V DC (load resistance, Minimum 100 k )
Output accuracy : Within 0.3% of the Transmission output span