52
Character
Name, Function, Setting Range
Factory Default
EVT4 alarm value
0
• Sets EVT4 alarm value.
Setting the value to 0 or 0.0 disables the function (except
Process high and Process low alarm)
.
Not available if No event is selected.
Available only when Alarm output is selected in [Event output EVT4
allocation].
• Setting range: Refer to (Table 8.1.2-1) on p.53.
EVT4 high limit alarm value
0
• Sets EVT4 high limit alarm value.
Setting the value to 0 or 0.0 disables the function (except
Process high and Process low alarm)
.
Not available if No event is selected.
Available only when Alarm output is selected in [Event output EVT4
allocation].
For the independent alarms such as High/Low limits independent,
High/Low limit range independent and High/Low limits with standby
independent, the EVT alarm value matches the low limit side, and
EVT high limit alarm value matches the high limit side.
• Setting range: Refer to (Table 8.1.2-1) on p.53.
EVT5 alarm value
0
• Sets EVT5 alarm value.
Setting the value to 0 or 0.0 disables the function (except
Process high and Process low alarm)
.
Not available if No event is selected.
Available only when Alarm output is selected in [Event output EVT5
allocation].
• Setting range: Refer to (Table 8.1.2-1) on p.53.
EVT5 high limit alarm value
0
• Sets EVT5 high limit alarm value.
Setting the value to 0 or 0.0 disables the function (except
Process high and Process low alarm)
.
Not available if No event is selected.
Available only when Alarm output is selected in [Event output EVT5
allocation].
For the independent alarms such as High/Low limits independent,
High/Low limit range independent and High/Low limits with standby
independent, the EVT alarm value matches the low limit side, and
EVT high limit alarm value matches the high limit side.
• Setting range: Refer to (Table 8.1.2-1) on p.53.