9. Operation
9.1 Starting Operation
After the unit is mounted to the control panel and wiring is completed, operate the unit
following the procedure below.
(1) Turn the power supply to the unit ON.
After the power is turned on, the PV Display indicates the input type, and the SV/MV/
TIME Display indicates the input range high limit value (thermocouple, RTD inputs) or
scaling high limit value (DC voltage, current inputs) for approximately 3 seconds.
See (Table 9.1-1).
(Table 9.1-1)
Sensor Input
PV Display SV/MV/TIME
Display
PV Display SV/MV/TIME
Display
K
J
R
S
B
E
T
N
PL-
C(W/Re5-26)
Pt100
JPt100
Pt100
JPt100
Pt100
Pt100
4 to 20 mA DC
0 to 20 mA DC
0 to 10 mV DC
-10 to 10 mV DC
0 to 50 mV DC
0 to 100 mV DC
0 to 1 V DC
0 to 5 V DC
1 to 5 V DC
0 to 10 V DC
Scaling high limit value
During this time, all outputs and indicators are in OFF status.
Control will then start, indicating as follows.
•
Fixed value control status
The PV Display indicates PV, the SV/MV/TIME Display indicates SV, and the
MEMO/STEP Display indicates the memory number if selected in [Event
input allocation].