38
•
Alarm output setting items [When Alarm output (001 to 012) is selected]
Character
Name, Function, Setting Range
Factory Default
(*)
Alarm hysteresis
1.0
• Sets Alarm hysteresis.
• Setting range: 0.1 to 1000.0 ( )
DC voltage, current inputs: 1 to 10000 (The placement of the
decimal point follows the selection.)
(*)
Alarm delay time
0 seconds
• Sets Alarm action delay time.
When setting time has elapsed after the input enters the Alarm output
range, the Alarm is activated.
• Setting range: 0 to 10000 seconds
(*)
Alarm Energized/De-energized
Energized
• Selects Alarm action Energized/De-energized status.
(Refer to “Alarm action Energized/De-energized”.)
•
: Energized
: De-energized
(*): If “001 (Alarm output; High limit alarm) to 012 (Alarm output; High/Low limits with
standby independent” is selected in [Event output EVT4 and EVT5 allocation],
their setting characters will be
xxx and
xxx.
[Alarm action Energized/De-energized]
When [Alarm Energized (
)] is selected, EVT1 output (terminals 9, 10)
is conductive (ON) while the EVT1 indicator is lit.
EVT1 output is not conductive (OFF) while EVT1 indicator is not lit.
When [Alarm De-energized (
)] is selected, EVT1 output (terminals 9, 10)
is not conductive (OFF) while EVT1 indicator is lit.
EVT1 output is conductive (ON) while EVT1 indicator is not lit.
High limit alarm (when Energized is set) High limit alarm (when De-energized is set)
(Fig. 7.3.4-2)
(Fig. 7.3.4-3)
For EVT4 and EVT5, the alarm action is the same as that of EVT1.
For EVT4, read “EVT4” for “EVT1”.
For EVT5, read “EVT5” for “EVT1”.
• EVT4 output: Terminals 29, 30
• EVT5 output: Terminals 28, 30
OFF
ON
EVT1 hysteresis
SV
+ EVT1 value
OFF
ON
SV
+ EVT1 value
EVT1 hysteresis