79
Indication performance
Base accuracy:
Thermocouple : Within 0.2% of each input span 1 digit,
However R, S inputs, 0 to 200 (32 to 392 ): Within 6 (12 )
B input, 0 to 300 (32 to 572 ): Accuracy is not guaranteed.
K, J, E, T, N inputs, less than 0 (32 ): Within 0.4% of input span 1 digit
RTD:
Within 0.1% of each input span 1 digit
Direct current: Within 0.2% of each input span 1 digit
DC voltage: Within 0.2% of each input span 1 digit
External setting input accuracy:
Within 0.2% of External setting input span
Cold junction temperature compensation accuracy:
Within 1 at 0 to 50
Input sampling period
: 125 ms (250 ms when EA or EV option is added)
Time accuracy:
Within 1.0% of the setting time
Control performance
Setting accuracy:
Based on the base accuracy and Cold junction temperature
compensation accuracy
Control action
PID control (with AT function)
PI control: When derivative time is set to 0
PD control (with Auto/Manual reset function): When integral time is set to 0
P control (with Auto/Manual reset function): When derivative and integral time are set to 0
ON/OFF control: When proportional band is set to 0 or 0.0
Proportional band: 0 to Input span ( )
DC voltage, current inputs: 0.0 to 1000.0%
(ON/OFF control when set to 0 or 0.0) (Default: 10 )
Integral time: 0 to 3600 seconds (OFF when set to 0) (Default: 200 seconds)
1 to 3600 seconds (When “FBP No” is selected in [FBP Yes/No])
Derivative time: 0 to 1800 seconds (OFF when set to 0) (Default: 50 seconds)
ARW:
0 to 100% (Default: 50%)
ON/OFF hysteresis: 0.1 to 1000.0 ( ) (Default: 1.0 )
DC voltage, current inputs: 1 to 10000 (The placement of the
decimal point follows the selection.)
MV high limit setting: 0 to 100% (Default: 100%)
MV low limit setting: 0 to 100% (Default: 0%)
Open output time: 0.1 to 1000.0 seconds (Default: 30.0 seconds)
Closed output time: 0.1 to 1000.0 seconds (Default: 30.0 seconds)
The output time corresponds to the MV 0 to 100%.
Open/Closed output dead band : 0 to 100% of the proportional band (Default: 10%)
Open/Closed output hysteresis : 0 to 100% of the proportional band (Default: 1%)
Control output
Relay contact:
1a x 2,
Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cos =0.4)
Electrical life: 100,000 cycles
FBP resolution:
1000 (corresponds to Fully Open and Fully Closed after
FBP adjustment.)
Feedback resistance:
100 to 10 k