To enter the Program Pattern group, follow the procedure below.
(1)
Press the
key in PV/SV Display Mode.
The unit proceeds to the Program Pattern group.
(2)
Press the
key.
The unit proceeds to ‘Step1 SV’.
Character
Name, Function, Setting Range
Factory Default
Step 1 SV
0
• Sets Step 1 SV.
• Setting range: Scaling low limit value to Scaling high limit value
Step 1 time
00:00
• Sets Step 1 time.
• Setting range: 00:00 to 99:59
Step 1 wait value
0
• Sets Step 1 wait value.
This function prevents the step from proceeding to the next one until
PV enters the range of SV Wait value regardless of the step time.
Setting the value to 0 or 0.0 disables the function.
• Setting range: 0 to Converted value of 20% of input span
Step 1 EVT1 alarm value
0
• Sets Step 1 EVT1 alarm value.
Setting the value to 0 or 0.0 disables the function (except
Process high and Process low alarm).
Not available if No event is selected.
Available only when Alarm output is selected in [Event output EVT1
allocation].
• Setting range: Refer to (Table 8.1.2-1) on p.53.
Step 1 EVT1 high limit alarm value
0
• Sets Step 1 EVT1
high limit alarm value.
Setting the value to 0 or 0.0 disables the function (except
Process high and Process low alarm)
.
Not available if No event is selected.
Available only when Alarm output is selected in [Event output EVT1
allocation].
For the independent alarms such as High/Low limits independent
alarm and High/Low limit range independent alarm, the EVT alarm
value matches the low limit side, and EVT high limit alarm value
matches the high limit side.
• Setting range: Refer to (Table 8.1.2-1) on p.53.
Step 1 EVT4 alarm value
0
• Sets Step 1 EVT4 alarm value.
Setting the value to 0 or 0.0 disables the function (except
Process high and Process low alarm)
.
Not available if No event is selected.
Available only when Alarm output is selected in [Event output EVT4
allocation].
• Setting range: Refer to (Table 8.1.2-1) on p.53.