172
Operating Instructions – MOVIGEAR® SNI-B
9
Local mode (only in conjunction with optional plug connector)
Operation
9.1.2
Activating local mode
Set DIP switch S2/3 to "ON" (also see "Startup" chapter). This allows for local mode with
optional plug connector "X5131" (also see "Electrical Installation" chapter).
The setting of the DIP switch determines whether motion control input "DI04" can be
used to switch between sensor inputs and local mode irrespective of the set function.
When DIP switch S2/3 is set to "ON" and motion control input DI04 is set to "1", then
motion control inputs DI01 to DI03 are used for local mode with the following functions:
9.1.3
Deactivating local mode
INFORMATION
Local mode can only be activated when the drive is not enabled.
2685981451
Motion control inputs
Functionality when DIP switch S2/3 = ON
DI01
CW/stop
DI02
CCW/stop
DI03
Setpoint selection
"0" = Setpoint n_f1 active (parameter 10096.35, factory set to 1500 rpm)
"1" = Setpoint n_f2 active (parameter 10096.36, factory set to 200 rpm)
DI04
Switching between local mode / automatic mode
ON
DIP
1 2 3 4
S2
Use of motion control
inputs
OFF
= Used as sensor inputs
ON = Used for local mode
WARNING
Risk of injury if the drive starts up unintentionally.
Severe or fatal injuries.
• Before deactivating local mode, take measures to prevent the drive unit from start-
ing up unintentionally, e.g. activating "STO".
• Take additional safety precautions depending on the application to avoid injury to
people and damage to machinery.