Operating Instructions – MOVIGEAR® SNI-B
109
6
Starting up the GIO13B application option
Startup
DIP switch S3
The following figure shows the possible settings for DIP switch S3:
INFORMATION
If the current input mode is set with DIP switch "S3/3 = ON", the current resistor must
be activated with DIP switch "S3/4 = ON".
INFORMATION
Notice: Setting DIP switch S3/2 to "ON" will overwrite any IPOS program on the com-
mand pcb.
9007201137839115
Refresh times of primary frequency inputs depending on the set scaling frequency
Scaling frequency
[Hz]
Refresh times [ms]
LFI mode = trace A
LFI mode = traces A + B
1
500
250
2
250
125
5
100
50
10
50
25
20
25
12
40
12
6
80
6
3
120
3
2
ON
DIP
1 2 3 4
S3
S3/4: Analog input current resistor
ON =
Enabled
OFF
=
Disabled
S3/3: Analog input mode
ON
= Current input
OFF
= Voltage input
S3/2: IPOS download
ON
= Download of IPOS program to the command pcb
and start of IPOS program
OFF
= No action
S3/1: Primary frequency input mode
ON =
Track
A/B
OFF
=
Track
A
00
I