Operating Instructions – MOVIGEAR® SNI-B
183
10
Error table
Service
Fault 39
"Reference travel" error
Output stage
inhibit / locked
The reference cam is missing or does not switch
→
Check reference cam
Limit switches are connected incorrectly
→
Check limit switch connection
Reference travel type was changed during reference travel
→
Check reference travel type setting and required parameters.
Fault 40
Boot synchronization error
Output stage
inhibit / locked
Command PCB defective or connection to command PCB interrupted.
→
Contact SEW Service
Fault 41
Watchdog option error
Output stage
inhibit / locked
Command PCB defective or connection to command PCB interrupted.
→
Contact SEW Service
Option defective or connection to option interrupted.
→
Check whether an option is installed
→
Replace the option
Fault 42
Lag error positioning
Output stage
inhibit/waiting
•
Emergency stop ramp too short
→
Extend emergency stop ramp
•
P-component of positioning controller too small
→
Increase P-com-
ponent
•
Value of lag error tolerance too small
→
Increase lag error tolerance
→
Check whether mechanical components can move freely
Fault 43
Timeout – manual opera-
tion via any interface
Parameterizable
•
Connection between unit and PC interrupted
→
Check and re-
establish connection.
Fault 44
Ixt utilization / UL monitor-
ing
Output stage
inhibit/waiting
Output stage overload
→
Reduce the load on the drive
Reset error by switching the unit off or via error reset function.
Fault 45
Initialization error
Motor-inverter assignment
incorrect
Output stage
inhibit / locked
•
Hardware defective
→
Contact SEW Service.
•
Incorrect motor/inverter assignment
→
Replace electronics.
Fault 46
Timeout – internal SBus
connection between com-
mand PCB and power sec-
tion
Emergency
stop/waiting
•
Contact SEW Service.
Fault 47
Communication interrupted
during cyclical data
exchange.
Parameterizable
Power section error
•
No SBus connection between MOVIGEAR
®
inverter and controller.
Check and establish connection, especially terminating resistor.
•
EMC influence Check shielding of data lines and improve, if neces-
sary.
•
Protocol period between the individual telegrams is longer than the
set time (timeout time). Shorten telegram cycle.
Command PCB error
•
Connection to AS-Interface master interrupted
→
Check and re-
establish connection.
•
Connection between AS-Interface option and command PCB inter-
rupted
→
Contact SEW Service.
Fault 50
Internal voltage supply too
low
Output stage
inhibit / locked
•
Hardware defective
→
Contact SEW Service.
Fault 52
Machine control error
Output stage
inhibit / locked
•
Operation without encoder a speed that is too low
→
Increase
speed
•
Load too high in controlled operation
→
Reduce load on the drive
Reset error by switching the unit off or via error reset function.
Consult SEW Service if the error recurs.
Fault 53
CPU error
Output stage
inhibit / locked
Reset error by switching the unit off or via error reset function.
Consult SEW Service if the error recurs.
Fault 77
IPOS error
Output stage
inhibit / locked
Faulty IPOS program (e.g. invalid command)
→
Correct program
Reset error by switching the unit off or via error reset function.
Fault 89
Only in conjunction with
DRC electronic motor:
Brake overtemperature
Output stage
inhibit / locked
Brake coil not sufficient to dissipate the regenerative energy.
→
Use braking resistor
Wrong size of braking resistor selected.
→
Use larger braking resistor
Error code
Description
Switch-off
response
Cause/solution