6
Electrical installation
Protective measures against electrical hazards
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
62
Procedure
Always ground the device using the shortest possible route.
[1]
[5]
[2]
[3]
[4]
[1]
[6]
[2]
[3]
[4]
33335044235
[1]
Device
[4]
Screw, self-tapping
[2]
Terminal clip
[5]
HF litz wire (ground strap)
[3]
Serrated lock washer
[6]
PE conductor
The connection points for ground connection or equipotential bonding are on the
corners of the device [1]. The connection points are marked with a "ground" icon.
1. Push the terminal clip [2] onto the connection point.
2. Take a screw [4] and push a serrated lock washer [3], the crimp cable lug for the
PE [6] or the HF litz wire [5] and another serrated lock washer [3] onto it.
3. Tighten the screw [4] with a maximum tightening torque of 5 Nm using a wrench.
26596598/EN – 10/2020