10
Technical data
Communication and control unit
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
170
10.10
Communication and control unit
10.10.1 Control type
INFORMATION
The overall output power of the 24 V voltage supply at the plug connectors for buses
and digital inputs/outputs must not exceed 48 W.
Type
MNC45A
Engineering
Engineering is performed via the Ethernet service interface and the plant
software MOVIVISION
®
.
Binary inputs
Compatibility
PLC-compatible according to IEC 61131-2:2008-04 type 3 "Standard oper-
ating ranges for digital inputs (current sinking)"
Internal resistance
≈ 4.5 kΩ
Current consumption
≈ 5.3 mA
High level
DC +13 V – +30 V
Low level
DC -3 V – +5 V
Activation delay
Typ. 250 μs
Power off delay
Typ. 250 μs
Binary outputs
Compatibility
PLC-compatible according to IEC 61131-2:2008-04 "Rated values and op-
erating ranges (DC) for current-sourcing digital DC outputs"
All outputs are protected against short circuit and overload and external-
voltage-proof up to 30 V.
Nominal current
Max. DC 500 mA per digital output
Output current limit
Maximum 1.1 A
Inductive loads
Dissipation of inductive switch-off energy up to 1 J per output at X5001
Freewheeling diodes are not integrated.
Low level
DC 0 V
High level
DC 24 V ± 10%
Activation delay
Typ. 100 μs
Power off delay
Typ. 150 μs
24 V power supply of the buses
Nominal voltage
DC 24 V ± 10%
Nominal current
Max. DC 500 mA per connection
Output current limit
Maximum 1.1 A
The continuous output current must not exceed 500 mA.
26596598/EN – 10/2020
Summary of Contents for MOVIPRO PHC2 Series
Page 2: ...SEW EURODRIVE Driving the world...
Page 185: ...Index X5502 143 26596598 EN 10 20 Operating Instructions MOVIPRO PHC2 A A M1 E45C C5 185...
Page 186: ......