51
P
OSITIVE
P
OWER
/E
NERGY
M
EASUREMENT
R
EGISTERS
Modbus
Offset
Register
Description
* System=sum of three phases
46001
6000
Positive kWh System LSW
System Positive True Energy LSW (kWh, resettable)
46002
6001
Positive kWh System MSW
System Positive True Energy MSW (kWh, resettable)
46003
6002
Positive kW System
System Positive Instantaneous Positive True Power
(kW) (net sum of all individual kWs, if sum is negative
value=0)
46004
6003
kW Demand System Max
System Maximum Demand (peak demand).
46005
6004
kW Demand System Now
Average Power (kW) for most recent demand window
46006
6005
Positive kW System Max
System Net Highest Instantaneous Positive Draw
Since Reset (kW, resettable)
46007
6006
Positive kW System Min
System Net Lowest Instantaneous Positive Draw Since
Reset (kW, resettable)
46008
6007
Positive kVARh System LSW
System Net Positive Reactive Energy LSW (kVARh,
resettable)
46009
6008
Positive kVARh System MSW
System Net Positive Reactive Energy MSW (kVARh,
resettable)
46010
6009
Positive kVAR System
System Net Instantaneous Positive Reactive Power
(kVAR) (net sum of all individual kVARs, if sum is
negative value=0)
46011
6010
kVAh System LSW
System Apparent Energy, LSW (resettable)
46012
6011
kVAh System MSW
System Apparent Energy, MSW (resettable)
46013
6012
kVA System
System Instantaneous Apparent Power
46014
6013
Positive Displacement PF
System
System Positive Displacement Power Factor (dPF);
Register is 100x actual value (If the System dPF
(44014) is positive, this register will contain that value
else it will be zero)