75
Modbus Output Port Registers
Refer to the following two tables to configure the Power Patrol output ports when using the Modbus
protocol.
Modbus
Register
Offset
Register Name
Detailed Description
44402
4401/5301
Port 1 output control
when used as an on/off—
open/closed switch
0 = output LOW (closed)
1 = output HIGH (open) [default]
Register 45110 must = 0 to use
45110
5109/5309
Digital Port 1
Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an
on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
45111
5110/5310
Port 1 pulse output relay
type
0 = normally open (HIGH)
1 = normally closed (LOW)
Table C-2: Modbus Digital Port Pulse Output
BACnet Output Port Objects
Refer to the following two tables to configure the Power Patrol output ports when using the BACnet
protocol.
SPP
Object
Identifier
Name
Detailed Description
13020
Port 1 output control when used as an
on/off—open/closed switch
0 = output LOW (closed) 1 = output HIGH
(open) [default]
Object 13100 present value must = 0 to use
13100
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an
on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
13110
Port 1 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)
Table C-3: BACnet Digital Port 1 Pulse Output