68
Object
Identifier
Name
Description
* System=sum of three phases
8050
kVA Demand System Now
Average kVA for most recent demand window (resettable). Displays
the default value after a CAM or reset, or power cycle. Updates
every min thereafter. True demand value takes a demand period to
get to actual value. (Unsigned/Absolute)
9000
Displacement PF System
System Total Power Factor (PF) (Signed)
9030
Apparent PF System
System Total Power Factor (PF) (Signed)
9060
Displacement PF L1
Individual Phase displacement Power Factor (PF)
9090
Displacement PF L2
“
9120
Displacement PF L3
“
9150
Apparent PF L1
Individual Phase apparent Power Factors (PF)
9180
Apparent PF L2
“
9210
Apparent PF L3
“
10000
Measured Line Frequency
Line Frequency (Hz)
10010
Time Since Reset
Seconds since accumulator registers were reset.
P
OSITIVE
P
OWER
/E
NERGY
M
EASUREMENT
O
BJECTS
Object
Identifier
Name
Description
* System=sum of three phases
1080
kW System Average Positive
Equals kWh System Positive / (Time Since Reset /3600 seconds/Hr)
(resettable) (Signed Net)
1110
kW System Maximum Positive
System Highest Instantaneous Positive Draw Since Reset (kW)
(Signed Net)
1140
kW System Minimum Positive
System Lowest Instantaneous Positive Draw Since Reset (kW,
resettable)
2010
kWh System Total Positive
System True Energy (kWh) Positive (Signed Net)
2040
kWh L1 Positive
Individual Phase True Energy (kWh) (Signed)
2070
kWh L2 Positive
“
2100
kWh L3 Positive
“
6010
kVARh System
System Total Reactive Energy (Signed Net)