79
Address
Units
≤ 100A
101 – 400A
401 – 800A
801 – 1600A
1601 – 32,000A
40014
aPF L2
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
40015
aPF L3
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
40016
VOLTS L1-L2
0.03125
0.03125
0.03125
0.03125
0.03125
40017
VOLTS L2-L3
0.03125
0.03125
0.03125
0.03125
0.03125
40018
VOLTS L3-L1
0.03125
0.03125
0.03125
0.03125
0.03125
40019
VOLTS L1-N
0.015625
0.015625
0.015625
0.015625
0.015625
40020
VOLTS L2- N
0.015625
0.015625
0.015625
0.015625
0.015625
40021
VOLTS L3- N
0.015625
0.015625
0.015625
0.015625
0.015625
40022
AMPS L1
3.9063exp-3
0.015625
0.03125
0.0625
0.125
40023
AMPS L2
3.9063exp-3
0.015625
0.03125
0.0625
0.125
40024
AMPS L3
3.9063exp-3
0.015625
0.03125
0.0625
0.125
40025
kW
0.004
0.016
0.032
0.064
0.128
40026
kW
0.004
0.016
0.032
0.064
0.128
40027
kW
0.004
0.016
0.032
0.064
0.128
Table D-3: Veris Multipliers for Integer Registers 40001-40027
Per the Veris implementation, to obtain true engineering units, the values returned from the registers in
Table G-2 must be multiplied by the scaling values listed in Table G-3.
For example, if the Power Patrol has 100A CTs connected to it, the system reactive power (kVAR) is
calculated by:
Read register 40004
Multiply the value returned from register 40004 by 0.004