58
Modbus
Offset
Register
Detailed Description
* System=sum of three phases
47042
7041
kVAh L1 MSW
Individual Phase Apparent Energy MSW (kVAh,
resettable)
47043
7042
kVAh L2 LSW
“
47044
7043
kVAh L2 MSW
“
47045
7044
kVAh L3 LSW
“
47046
7045
kVAh L3 MSW
“
47047
7046
kVA L1
Individual Phase Instantaneous Apparent Powers
(kVA)
47048
7047
kVA L2
“
47049
7048
kVA L3
“
47050
7049
Negative Displacement PF L1
Individual Phase Negative Displacement Power
Factors (dPF); Register is 100x actual value (If the
Individual dPF(44050) is Negative, this register will
contain that value else it will be zero)
47051
7050
Negative Displacement PF L2
“
47052
7051
Negative Displacement PF L3
“
47053
7052
Negative Apparent PF L1
Individual Phase Negative Apparent Power Factors
(aPF); Register is 100x actual value (If the Individual
aPF (44053) is Negative, this register will contain that
value else it will be zero)
47054
7053
Negative Apparent PF L2
“
47055
7054
Negative Apparent PF L3
“
47056
7055
Amps L1
Individual Phase Instantaneous Currents (A)
47057
7056
Amps L2
“
47058
7057
Amps L3
“
47059
7058
Volts L1 to Neutral
Individual Instantaneous Phase to Neutral Voltages
(V)
47060
7059
Volts L2 to Neutral
“