56
Modbus
Offset
Register
Detailed Description
* System=sum of three phases
47011
7010
kVAh System LSW
System Apparent Energy LSW (kVAh, resettable)
47012
7011
kVAh System MSW
System Apparent Energy MSW (kVAh, resettable)
47013
7012
kVA System
System Instantaneous Apparent Power (kVA)
47014
7013
Negative Displacement PF
System
System Negative Displacement Power Factor (dPF);
Register is 100x actual value (If the System dPF
(44014) is Negative, this register will contain that
value else it will be zero)
47015
7014
Negative Apparent PF System
System Negative Apparent Power Factor (aPF);
Register is 100x actual value (If the System aPF
(44015) is Negative, this register will contain that
value else it will be zero)
47016
7015
Amps System Avg
Average of the current in all phases.
47017
7016
Volts Line to Line Avg
Average of the system line to line voltages.
47018
7017
Volts Line to Neutral Avg
Average of the system line to neutral voltages.
47019
7018
Volts L1 to L2
Individual phase to phase voltages.
47020
7019
Volts L2 to L3
“
47021
7020
Volts L3 to L1
“
47022
7021
Measured Line Frequency
Line frequency x 10 (e.g., 602 = 60.2 Hz). On startup,
20 point averaging array is filled with first frequency
read.