55
Modbus
Offset
Register
Description
* System=sum of three phases
46082
6081
kVA Demand System Maximum
Maximum Instantaneous kVA Demand (kW,
resettable).
46083
6082
kVA Demand System Now
System Average kVA Demand for the most recent
(current) Demand Window (resettable).
46084
6083
kVAR Demand System Max
System Maximum kVAR Demand (kVAR, resettable). It
displays the default value after a CAM until 1 demand
window elapses. After a power cycle or CPU reset the
value is not reset but it does not update again until 1
demand window elapses.
N
EGATIVE
P
OWER
/E
NERGY
M
EASUREMENT
R
EGISTERS
Modbus
Offset
Register
Detailed Description
* System=sum of three phases
47001
7000
Negative kWh System LSW
System Negative True Energy LSW (kWh, resettable)
47002
7001
Negative kWh System MSW
System Negative True Energy MSW (kWh, resettable)
47003
7002
Negative kW System
System Negative Instantaneous Negative True Power
(kW) (net sum of all individual kWs, if sum is positive
value=0)
47004
7003
kW Demand System Max
System Maximum Demand (peak demand).
47005
7004
kW Demand System Now
Average Power (kW) for most recent demand window
47006
7005
Negative kW System Max
System Net Highest Instantaneous Negative Draw
Since Reset (kW, resettable)
47007
7006
Negative kW System Min
System Net Lowest Instantaneous Negative Draw
Since Reset (kW, resettable)
47008
7007
Negative kVARh System LSW
System Net Negative Reactive Energy LSW (kVARh,
resettable)
47009
7008
Negative kVARh System MSW
System Net Negative Reactive Energy MSW (kVARh,
resettable)
47010
7009
Negative kVAR System
System Net Instantaneous Negative Reactive Power
(kVAR) (net sum of all individual kVARs, if sum is
positive value=0)