46
Modbus
Offset
Register
Description
44604
4603
Volts Multiplier
Multiply volts values by this scalar. Use with Step-
down Transformer. Affects all parameters that use
volts (i.e., kW)
44605
4604
Amps Multiplier
Multiply amps value by this scalar. For use with x:5A
CTs and single let monitoring of a three phase load.
Affects all parameters that use amps (i.e, kW)
44607
4606
Service Type
A value of 0x0001 configures the meter for DELTA
A value of 0x0000 configures the meter for WYE
44609
4608
Set Line Frequency
Line frequency setting for metering: 50=50 Hz,
60=60Hz
44612
4611
Communications Settings
Write 1833 to change to BACnet mode
50100
10099
CT1 Integer
Integer part of CT1
50101
10100
CT1 Decimal
Fractional part of NV_CT1
50125
10124
CT1 Type
Select 1=mV or 2=Rogowski CT1s
50199
10198
CT1 Phase Shift
Phase Shift X 100 +/-
50200
10199
CT2 Integer
Integer part of CT2
50201
10200
CT2 Decimal
Fractional part of NV_CT2
50225
10224
CT2 Type
Select 1=mV or 2=Rogowski CT2s
50299
10298
CT2 Phase Shift
Phase Shift X 100 +/-
50300
10299
CT3 Integer
Integer part of CT3
50301
10300
CT3 Decimal
Fractional part of NV_CT3
50325
10324
CT3 Type
Select 1=mV or 2=Rogowski CT3s
50399
10398
CT3 Phase Shift
Phase Shift X 100 +/-
P
ULSE
O
UTPUT
/I
NPUT
R
EGISTERS
Modbus
Offset
Register
Description
44402
4401
Port 1 output control when
used as an on/off—open/closed
switch
0 = output LOW (closed)
1 = output HIGH (open) [default]
Register 45110 must = 0 to use
45110
5109
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses