AC SOURCE controls the grid connection in three ways:-
Set the
Grid Input Limit
to the maximum draw from the grid supply. This limit will
override the AC Source Power limit configured within the Quick Start settings. Any
AC Load demand above this limit will be supplied from the Battery plus renewable
energy sources (Battery / RE system).
This limit will only be breached if the AC Load demands more power than is
available from the
Battery / RE system
or if the SoC S
upport Limit within the Priority
schedule is reached.
Set the
Grid Export Limit
to the maximum power to be put into the grid. This limit
will override the AC Source Power limit configured within the Quick Start settings.
This limit only applies to Managed AC Coupling or DC Coupled PV and must be set
to the maximum (15kW for SPMC models and 30kW for SPLC models) when using
Generic AC Coupled supply.
Enable
Grid Disconnect
to switch the SP PRO into standalone mode and operate
completely on the Battery plus any renewable energy generation.
No grid export or
grid battery recharge is possible when the
Grid Disconnect
is Enabled
The
Grid Disconnect
setting will be overridden if the SoC Support Limit within the
Priority schedule is reached or if Inverter Disconnect is Enabled.
The
Grid Disconnect
setting will be disabled and greyed out in all secondary
inverters in a Powerchain configuration. Only the System Manager (L1 manager)
controls this function.
INVERTER CONTROL manages the AC Load Battery Support by controlling the
amount and limit of battery support.
AC Load Support Limit
sets the maximum
AC Load power that can be supported
from the battery bank when the SP PRO is synchronised to the AC Source (Grid)
supply. This power does not include any contribution from AC or DC Coupled PV.
This limit is overridden to zero when the SoC Support Limit is reached.
SoC Support Limit
sets the minimum Battery SoC that the AC Load Support and
AC Source control will operate to. When the
SoC Support Limit
is reached any
discharge demand on the battery is diverted to the AC Source (Grid) supply. When
the SoC recovers by 20% of the battery’s discharge (e.g. back to 68% with a
SoC
Support Limit
setting of 60%) then the
AC Load Support Limit
will once again
apply.
Setting
Inverter Disconnect
to Enable switches the SP PRO into grid feed through
mode and operate completely from the Grid and AC Coupled PV. No DC Coupled
grid export, grid battery recharge or AC Load Support is possible during times
when the
Inverter Disconnect
is Enabled.
The
Inverter Disconnect
setting will be overridden if the AC Source (Grid) supply
falls outside
AC voltage and frequency tolerance. There will be short break in
supply (< 1.0 seconds) while the Inverter functions switches on-line to provide
back-up power.
The
Inverter Disconnect
setting will be disabled and greyed out in all secondary
inverters in a Powerchain configuration. Only the System manager controls this
function.
Summary of Contents for SP PRO 2i Series
Page 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Page 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Page 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Page 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...