SP LINK | Alert Messages
98
|
Doc #OI0005 Rev26 2020
Appendix One
Alert Messages
The SP PRO is continuously measuring and monitoring the power system to ensure correct system operation at
all times. When the SP PRO detects a problem with the power system it then:
1. Displays a message in the “Attention Required” area in SP LINK (In the Data View - Now tab).
2. Creates an entry in its data log memory. This data can be downloaded from the SP PRO and viewed in the
EVENTS tab of the Performance Data Viewer.
The table in this section outlines all the SP PRO ALERT type event messages, the most likely cause and
possible remedies.
Only the ALERT events are listed - They are listed in alphabetical order.
Alerts and attention
required messages
Meaning and diagnostic
Action
Configuration
settings>
AC Source - Safety
Monitor Alert - Neutral
and Earth are not at
same potential
The inverter has detected either a
poor EN connection or missing EN
connection in the AC Source wiring.
Call system installer to check
the voltage between the Earth
and Neutral of the AC Source
connections at the Inverter. If
voltage > 1VAC then track down
the wiring fault.
Service Settings
> AC Input
Safety Monitor
(group).
AC Source - Safety
Monitor Alert cleared
Above condition has cleared
Battery - Hi Battery
Alert
Battery voltage has risen above the Hi
Battery Alert Voltage
Call system installer to check
the correct operation of any
DC charge controllers. Check
communications between
SP PRO and grid inverter in
Managed AC coupled system.
Check all battery system
connections and check for faulty
cells in battery bank.
Battery > Hi
Battery Alert
Battery - Hi Battery
Alert Clear
Battery voltage has dropped below the
Hi Battery Alert Clear Voltage clearing
the above condition
Battery > Hi
Battery Alert
Clear
Summary of Contents for SP PRO 2i Series
Page 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Page 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Page 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Page 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...