SP LINK | Performance Monitoring
84
|
Doc #OI0005 Rev26 2020
Technical Data Tab
The
TECHNICAL DATA
tab provides you with information relating to maintenance and updating the SP PRO.
Current is a measurement of the current in the battery bank. A positive
(+) value, the battery is charging. A negative (-) value, the battery is
discharging.
Sense Voltage is a measurement of the battery voltage at the battery
terminals (When using a managed battery or when the battery sense/pre-
charge wiring is installed)
Target Charge Current and Target Charge Volts Show the present
temperature compensated charge current and voltage of the SP PRO
battery charger.
DC Inverter Voltage is a measurement of the battery voltage within the
SP PRO
Power is the amount of power presently drawn from the battery bank and
is used in conjunction with Cable Loss to determine its significance.
Midpoint Voltage is a measurement of half the battery voltage at the
battery terminals (when the battery sense/pre-charge wiring is installed) If
this value is not half the Sense Voltage then the batteries need equalising
or there is a faulty cell.
Midpoint Error is a measurement of the error in the midpoint voltage as a %.
Cable Loss is the amount of power that is dissipated in the battery cabling, fusing and terminal system. A high
reading could indication a problem with the battery terminals, battery connection to the SP PRO or inadequate
cable sizing.
Cable Loss % is the Cable loss as a percentage of the Battery power at that time.
SoC % is the State of Charge of the battery bank. 100% SoC is a full battery.
Days to Recharge and Days Since Recharge - If Periodic Recharge is enabled these readings track the
days since the last battery recharge and how many days before the next battery recharge.
Charger Lockout Requested indicates when the charger is off and there is no charging from the SP PRO.
Summary of Contents for SP PRO 2i Series
Page 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Page 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Page 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Page 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...