SP LINK | Alert Messages
Doc #OI0005 Rev26 2020
|
99
Alerts and attention
required messages
Meaning and diagnostic
Action
Configuration
settings>
Battery - Mid Point
Fault - Outside Range
after Equalise
Battery Mid Point Voltage is outside
Mid Point Range after an equalise has
been performed. Battery bank may
have faulty cell.
Call installer to check for faulty
cells in the battery bank or
for poor battery connections
between cells and between
battery bank and SP PRO
Battery >
Midpoint
Monitoring
Battery - Mid Point
Fault cleared
Above condition has cleared
Battery - Outside Mid
Point Range
Battery Mid Point Voltage is outside
Mid Point Range. Battery bank may
have faulty cell or need equalise
Initiate an equalise charge from
the Service Settings tab in SP
LINK (Battery Equalise section).
If problem persists then call
installer to check for faulty cells
in the battery bank or for poor
battery connections between
cells and between battery bank
and SP PRO.
Battery >- Mid
Point Range.
Battery - Within Mid
Point Range
Above condition has cleared
Battery > Mid
Point Range.
Battery - Over Temp
Protection Alert
The battery temperature has risen
above the Over Temp Protection limit
Immediately turn SP PRO to
IDLE (long press of ON button
on front panel). Call installer
to check battery temperature
sensor is correctly installed,
batteries charge parameters
are correct and that all charging
sources are operating correctly.
Installer to check that there are
no faulty cells in the battery
bank and to take measures
to reduce battery ambient
temperature.
Battery > Over
Temp Protection
> Limit Charge
Above.
Battery - Over Temp
Protection Alert cleared
The battery temperature has dropped
below the Over Temp Protection limit
Battery > Over
Temp Protection
> Limit Charge
Above..
Battery Management
- Alarm
The Battery Management System
within the battery has sent an alarm
to the SP PRO
Battery Management
- Alarm Cleared
The above alarm has cleared
Look in the Data View >
Battery Management tab for
details about the fault.
Charger - Battery
Capacity Alert -
Provided 120%
Capacity and voltage
target not achieved
Battery is not charging as fast as
expected. The battery SoC has risen
but the battery voltage is not matching
the expected SoC
Call your installer to check
battery condition and for shorted
or weak cells.
Battery Capacity
Charger - Battery
Capacity Alert cleared -
Voltage target achieved
The expected battery voltage target
has now been achieved. Batteries now
charging as expected.
Generator Controller
- Generator Fault Alert -
Stop generator
The Generator Fault input has been
asserted. Generator will be stopped if it
is running
Call appropriately qualified
personnel to diagnose and
rectify the generator fault.
Inputs/Outputs
> Generator
fault input
Generator Controller -
Generator Fault Alert
cleared
The Generator Fault input has been
cleared. Generator will start again as
required
Inputs/Outputs -
Generator fault
input
Generator Controller -
Low Fuel Alert
The Generator Low Fuel input has
been asserted. Generator will continue
to run
Fill generator fuel tank.
Inputs/Outputs -
Generator Low
Fuel input
Summary of Contents for SP PRO 2i Series
Page 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Page 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Page 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Page 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...