SP LINK | Alert Messages
108
|
Doc #OI0005 Rev26 2020
Alerts and attention
required messages
Meaning and diagnostic
Action
Configuration
settings>
System - Hi
Temperature Shutdown
The inverter has reached its maximum
operating temperature and shut down.
Either the load is too high or the air
flow is obstructed.
Turn off some of the appliances
connected to the system.
Check fan filter in the base of
the SP PRO for obstructions.
Ensure there is free airflow
around the inverter. If problem
persists, contact your installer.
System - Hi
Temperature Shutdown
cleared
Above condition has cleared
System - AC
Coupled Inverter #1
communication Fault
The RS485 communications with AC
Coupled Inverter #1 has been lost for
longer than 18 hours. It is normal to
lose communications overnight when
the AC Coupled Inverter shuts down so
loss for longer than 18 hours indicates
a fault.
Contact your installer to come
and check all the RS485
cables and wireless devices
between the SP PRO inverter
and Selectronic Certified grid
inverter.
System - AC
Coupled Inverter #1
communication Fault
Cleared
Above condition has cleared
System - AC
Coupled Inverter #2
communication Fault
The RS485 communications with AC
Coupled Inverter #2 has been lost for
longer than 18 hours. It is normal to
lose communications overnight when
the AC Coupled Inverter shuts down so
loss for longer than 18 hours indicates
a fault.
Contact your installer to come
and check all the RS485 cables
and wireless devices between
the SP PRO inverter and
the Selectronic Certified grid
inverter.
System - AC
Coupled Inverter #2
communication Fault
Cleared
Above condition has cleared
System - AC
Coupled Inverter #3
communication Fault
The RS485 communications with AC
Coupled Inverter #3 has been lost for
longer than 18 hours. It is normal to
lose communications overnight when
the AC Coupled Inverter shuts down so
loss for longer than 18 hours indicates
a fault.
Contact your installer to come
and check all the RS485 cables
and wireless devices between
the SP PRO inverter and
the Selectronic Certified grid
inverter.
System - AC
Coupled Inverter #3
communication Fault
Cleared
Above condition has cleared
System - AC
Coupled Inverter #4
communication Fault
The RS485 communications with AC
Coupled Inverter #4 has been lost for
longer than 18 hours. It is normal to
lose communications overnight when
the AC Coupled Inverter shuts down so
loss for longer than 18 hours indicates
a fault.
Contact your installer to come
and check all the RS485 cables
and wireless devices between
the SP PRO inverter and
the Selectronic Certified grid
inverter.
System - AC
Coupled Inverter #4
communication Fault
Cleared
Above condition has cleared
System - AC
Coupled Inverter #5
communication Fault
The RS485 communications with AC
Coupled Inverter #5 has been lost for
longer than 18 hours. It is normal to
lose communications overnight when
the AC Coupled Inverter shuts down so
loss for longer than 18 hours indicates
a fault.
Contact your installer to come
and check all the RS485 cables
and wireless devices between
the SP PRO inverter and
the Selectronic Certified grid
inverter.
Summary of Contents for SP PRO 2i Series
Page 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Page 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Page 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Page 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...