SP LINK | Using SP LINK
Doc #OI0005 Rev26 2020
|
21
Connection Settings
The connection settings (shown on the next page) show all the connection methods available between SP LINK
and the SP PRO. The connection settings need to be set depending on which other communication method is
being used. Details of the chosen connection type are stored with the site file.
Login Password
A Login Password is required for connecting to the SP PRO. SP LINK can only connect through
to the SP PRO with the correct password. The default password is “Selectronic SP PRO”. This is
different to the setting passcode.
Powerchain Inverter Assigments tab
This tab is used to set up an SP PRO Powerchain system. Once the SP PRO inverters have been installed in
a Powerchain configuration and before they have been configured, SP LINK is connected to the L1 SP PRO.
SP LINK will find all the SP PRO inverters in the system and list their serial numbers in this tab. The serial
numbers can then be dragged and dropped into their phase and “Save Assignments”.
Double clicking a serial number in this tab will cause the RED battery LEDs to flash on that
SP PRO.
For full details on installing a Powerchain system please refer to installation note:
IN0057_xx Installation of SP PRO Powerchain system.
When the SP PRO inverters are configured as a Powerchain system then all the inverters in the system can
be accessed via the System Manager (the SP PRO that is configured as L1 manager). Only one session of
SP LINK, connected to System Manager, is required to access all the SP PROs in the Powerchain.
Once connection is made via SP LINK, the Data View screens and the Service Settings for each inverter in the
Powerchain can be accessed by selecting the L1, L2, L3 or Split and manager/worker buttons (as applicable).
Summary of Contents for SP PRO 2i Series
Page 1: ...Instruction Manual for SP LINK Configuration and monitoring for SP PRO series 2i ...
Page 31: ...SP LINK Using SP LINK Doc OI0005 Rev26 2020 31 Blank Page ...
Page 91: ...SP LINK Performance Monitoring Doc OI0005 Rev26 2020 91 BLANK PAGE ...
Page 97: ...SP LINK Service Settings Doc OI0005 Rev26 2020 97 Blank Page ...