Technical Data Sheet
FI 72.0239.0320E
Page 98 / 108
APPENDIX
MODBUS EXCHANGES TABLE
SFX+NETWORK
This table is available for functions:
-
reading n registers (function 03h)
-
writing 1 register (function 06h)
-
writing n register (function 10h)
remarks:
-
A reading at a site which is not indicated returns an undetermined value.
-
If an entry request (function 06h or 10h) is made on a non-authorised register in writing or with a non-authorised value, this is ignored and an
exception message is sent back.
-
The maximum number of registers per exchange is limited to 125 for the 03h function and to 123 for the 10h function.
-
This table is general. Certain sites depend upon the operating functions of the chosen SFX+ configuration.
update: 26/03/2020
Modbus word
MW
Number
(address)
In DECIMAL
Modbus word
MW
Number
(address)
In HEXA-
DECIMAL
Content
A
v
a
il
a
b
le
i
n
re
a
d
in
g
A
v
a
il
a
b
le
i
n
w
ri
ti
n
g
1 (0)
1 (0)
Compressed air fault reset ("mini header" faults and "re-inflating" faults)
To each transition « 0 »
→
« 1 »
X
X
2 (1)
2 (1)
Initialization of the counters number of user cycles, number of user pulses,
Mini/maxi and average cycle time
To each transition « 0 »
→
« 1 »
X
X
3 (2)
3 (2)
1st fault reset of the stack
To each transition « 0 »
→
« 1 »
X
X
4 (3)
4 (3)
1st fault reset of the stack
To each transition « 0 »
→
« 1 »
Except if it’s a mini header fault or a re-inflation fault and if there is at least two headers in fault
(in this case: next fault)
X
X
5 (4)
5 (4)
“DP” Dust removal running order via MODBUS
Enter “1” to request the running
Enter “0” to cancel the request
(run in “OR” with a possible AON input)
Remark: The running mode of this order can be different according the SFX+ programming if a
« DP regulation running » below detailed is used.
X
X
6 (5)
6 (5)
Intensive running via MODBUS
Enter “1” for intensive running
Enter “0” to cancel the request
(run in “OR” with a possible AON input)
X
X
7 (6)
7 (6)
“Fan” Dust removal running order via MODBUS
Enter “1” to request the running
Enter “0” to cancel the request
(run in “OR” with a possible AON input)
(doing the number “fan stop” cycles if loss of the two running orders “fan” (via MODBUS and AON input)
X
X
8 (7)
8 (7)
Request of forced running via MODBUS
Enter “1” to request the forced running
Enter “0” not to ask forced running
(run in “OR” with a possible AON input)
(the SFX+ completes the current cycle, then a whole cycle is executed at each transition « 0 »
→
« 1 ». If
request stay to 1, we stay in forced running)
X
X
9 (8)
9 (8)
DP regulation running
Write « 0 » for local DP regulation running (the declogging running is given according DP AON input only,
whatever the DP running order may be via MODBUS)
Write « 1 » for remote DP regulation running (the declogging running is given according the DP order via
MODBUS only, whatever the DP AON input may be)
N.B.: this running mode is accessible according the SFX+ programming (see availability on the notice
appendix)
X
X
10 (9)
A (9)
Reset all the faults
To each transition « 0 »
→
« 1 »
X
X
11 (10)
B (A)
Request running with T2’
« 0 »
→
running with T2
« 1 »
→
running with T2’
X
X
12 (11)
C (B)
Request to cancel any forced running
To each transition « 0 »
→
« 1 »
X
X
13 (12)
D (C)
External running order via MODBUS
X
X
Summary of Contents for SFX+NETWORK
Page 21: ...Technical Data Sheet FI 72 0239 0320E Page 21 108 SIGNALLING...
Page 22: ...Technical Data Sheet FI 72 0239 0320E Page 22 108 CONNECTIONS CONNECTION EXAMPLE...
Page 24: ...Technical Data Sheet FI 72 0239 0320E Page 24 108 CONNECTIONS CONNECTION EXAMPLE...
Page 26: ...Technical Data Sheet FI 72 0239 0320E Page 26 108 CONNECTIONS CONNECTION EXAMPLE...
Page 28: ...Technical Data Sheet FI 72 0239 0320E Page 28 108 CONNECTIONS CONNECTION EXAMPLE...
Page 31: ...Technical Data Sheet FI 72 0239 0320E Page 31 108 CONNECTIONS CONNECTION EXAMPLE...
Page 34: ...Technical Data Sheet FI 72 0239 0320E Page 34 108 CONNECTIONS...
Page 37: ...Technical Data Sheet FI 72 0239 0320E Page 37 108 SFX MODULE POWER CONSUMPTION...
Page 38: ...Technical Data Sheet FI 72 0239 0320E Page 38 108...
Page 85: ...Technical Data Sheet FI 72 0239 0320E Page 85 108...